4.
Mitigation
Monitoring
and
Reporting
Program
Mitigation
Monitoring
and
Reporting
Matrix
(continued)
Significant
Impact
Being
Mitigated
Noise
and
Vibration
(cont.)
Exposure
of
underground
utilities
to
vibration
from
pile
driving
operations.
DSP,
DSP-V,
CPP,
&
CPP-V
scenarios
4.J-2c:
All
development
sites
requiring
pile
driving
shall
have
underground
utility
2
surveys
completed
before
a
building
permit
is
issued
to
demonstrate
that
pile
driving
will
be
located
a
minimum
15
feet
from
buried
utilities.
Underground
utilities
surveys
shall
be
submitted
to
the
City
for
review
and
consultation
with
affected
utilities
a
minimum
of
two
weeks
prior
to
commencement
of
construction
activities.
If
underground
utilities
are
identified
within
15
feet
of
proposed
pile
driving
activities,
alternative
pile
installation
methods
shall
be
required.
Alternative
methods
may
include
use
of
sonic
drivers
or
drilled
and
cast-in-place
piles.
All
pile
driving
shall
be
designed
so
as
to
result
in
peak
particle
velocity
of
less
than
4.0
in/sec
(100
mm/s)
at
the
location
of
underground
utilities.
Within
one
week
following
completion
of
pile
driving
activities,
a
post-construction
assessment
of
all
underground
utilities
within
30
feet
of
the
pile
driving
activity
shall
be
submitted
to
the
City
by
the
contractor,
confirming
that
no
damage
to
any
underground
utilities
occurred
as
the
result
of
the
pile
driving
activity.
Should
the
post-construction
assessment
determine
that
underground
utilities
were
damaged
by
pile
driving
activities,
such
damage
shall
be
repaired
by
the
contractor
to
the
satisfaction
of
the
City
and
affected
utility.
A
minimum
of
two
weeks
prior
to
commencement
of
construction
activities,
applicant(s)
for
development
requiring
pile
driving
shall
submit
to
the
City
an
underground
utility
survey
to
demonstrate
that
pile
driving
will
be
located
a
minimum
15
feet
from
buried
utilities.
Within
one
week
following
completion
of
pile
driving
activities,
the
pile
driving
contractor
shall
submit
to
the
City
a
post-construction
assessment
of
all
underground
utilities
within
30
feet
of
the
pile
driving
activity,
confirming
that
no
damage
to
any
underground
utilities
occurred
as
the
result
of
the
pile
driving
activity.
Should
the
post-
construction
assessment
determine
that
underground
utilities
were
damaged
by
pile
driving
activities,
such
damage
shall
be
repaired
by
the
contractor
to
the
satisfaction
of
the
City
and
affected
utility.
City
of
Brisbane
Building
Official
Prior
to
issuing
any
building
permit(s)
for
development
requiring
pile
driving,
the
City
Building
Official
shall
confirm
that
such
pile
driving
will
be
conducted
a
minimum
of
15
feet
away
from
all
underground
utilities.
Should
such
proposed
pile
driving
be
proposed
within
15
feet
of
an
underground
utility
line,
alternative
pile
installation
methods
shall
be
required.
The
City
Building
Official
shall
also
be
responsible
for
ensuring
that
pile-
driving
activities
are
designed
so
as
to
result
in
peak
particle
velocity
of
less
than
4.0
in/sec
(100
mm/s)
at
the
location
of
underground
utilities.
The
City
Building
Official
shall
review
the
required
post-construction
assessment
and
coordinate
with
affecting
utilities
to
determine
whether
any
damage
has
occurred
that
required
repair.
Should
the
City
Building
Official
determine
that
underground
utilities
were
damaged
by
pile
driving
activities,
the
Issuance
of
building
permit(s)
for
pile
driving
in
compliance
with
Mitigation
Measure
4.J-2c.
Mitigation
Measure
Responsibility
for
Implementation
Enforcement
Responsibility
Monitoring
Responsibility/
Frequency
Actions
Indicating
Compliance
2
Underground
utilities
include
electrical
lines,
irrigation
lines,
reclaimed
water
lines,
municipal
water
lines,
sewer
lines,
gravity
flow
facilities
(storm,
sanitary
and
laterals),
cable/communication
lines
and
gas
lines.
Brisbane
Baylands
Final
EIR
4-70
May
2015
Previous Next